RITTER Double Busbar Switchgear type GT5D

24 kV double busbar system with circuit-breakers in draw-out or fixed mounted design, busbar disconnectors and integrated pressure relief channel.

 

  • IEC 62271-200
  • up to 24 kV
  • up to 2500 A and 31,5 kA 3s
  • air insulated
  • metal enclosure, metal clad
  • Arc fault tested IAC AFLR 31,5 kA 1 s

 

The GT5D switchgear is an innovative, air-insulated double busbar switchgear in draw-out or fixed-mounted design. It covers the complete range of technical requirements at the 24 kV level. Due to the compact dimensions and the space-saving integrated pressure relief channel, the system is suitable for common switch rooms. With regard to the components used, such as protection, circuit breakers, current/voltage converters and secondary equipment, we can react flexibly to customer requirements.

Field of Application

As a circuit breaker system in grid, distribution and main stations for power companies, industry and public clients for switching transformers, motors, generators, overhead lines and cable routes.

Design

Metal-enclosed, air-insulated, factory-ready and type-tested. Compartmentalization is made between the busbar compartments of adjacent fields and between the busbar-, the circuit breaker- and cable connection compartments. Maximum personal and operational safety due to the LSC2B availability class, even for fixed ins­­­tallation. Classification for internal errors IAC AFLR. Cable voltage converters are installed on a mobile cassette. Also available as a fixed installation variant with an easy-to-remove, mobile circuit breaker.

Panel Types

Incoming feeder, outgoing feeder, busbar cross coupling; bus-section- and bus-riser panels with motorized busbar-disconnectors and draw-out or fixed mounted circuit breakers. Busbar measurements and busbar grounding switches are mounted on top  without a separate measuring field on the circuit breaker panels.

Dimensions

  • Width 800 mm to 1250 A operating output current
  • Width 1000 mm to 2500 A operating current without forced cooling
  • Depth 2000 mm
  • Height 3100 mm incl. integrated pressure relief channel
  • Height 3400 mm incl. busbar earthing switch or busbar voltage transformers box